| System according to type of grounding | TN | TN |
| Rated voltage | up to max 1000V | 400V AC |
| Transient overvoltages | Overvoltage category I-IV | II |
| Temporary overvoltage | See Table 8,9,10 | 2000V AC |
| Rated frequency | DC/50/60HZ | 50HZ |
| Short-circuit resistance | | up to 125A =10KA, 400A = 20KA |
| SCPD (Short-circuit protection device) in the supply | | mobile distributors are usually supplied via plug devices |
| Coordination between SCPD inside/outside the socket distributor | available/ install/ integrate | customer-dependent |
| Type of protection against electric shock (protection against electric shock due to contact inside the distributor during intended operation) | observe local requirements | basic protection |
| Type of protection against electric shock - fault protection (protection against faults in an INDU-ELECTRIC distro) | automatic disconnection/ protective insulation | article-dependent: automatic disconnection or protective insulation |
| Installation location | indoor/outdoor | article-dependent |
| Protection class | IP xx | IP 44 |
| Protection against mechanical impact | specify IK code | IK 10 |
| Resistance to UV radiation | required for outdoor installation | high resistance |
| Ambient temperature limits | Outdoor 25°C, Indoor 50% at 40°C | from -25°C to 45°C |
| Pollution degree | 1,2,3,4 | 3 (industrial environment) |
| Altitude | | 2000 meters |
| EMC environment | A/B | B |
| Special operating conditions such as EX zone, vibrations | | not defined |
| Requirements for storage and transport (type of transport, different environmental conditions, max. dimensions, packaging requirements) | none | see manual |
| Requirements for accessibility for operation, inspection, maintenance or expansion | none | inspection/maintenance only by qualified personnel |
| Separation of outgoing circuits | | via plug devices or connectors |
| Rated current of the switchgear assembly | | article-dependent |
| Rated diversity factor (RDF) | RDF for circuits / RDF for entire power distributor | RDF see INDU-ELECTRIC manual |
| Cross-section ratio between phase conductor and neutral | for currents in N up to 50% of phase conductors, otherwise special agreement required | phase conductor cross-section = neutral conductor cross-section |